ELLD is a pressure-based system that uses line information to monitor changes in pressure. It determines if a line is tight or if there is a leak and will provide 3.0 gph hourly, 0.2 gph monthly, and 0.1 gph annual precision line leak detection.
With ELLD, AUTO-LEARN® technology automatically learns the pressure characteristics of each pipeline for precision leak detection.
As a standard feature, Statistical Line Leak Detection (SLLD) allows busy sites with high fuel sales volume and very few quiet periods of no dispensing to achieve 0.2 gph leak testing.
ELLD is capable of monitoring up to approximately 312 gallons of rigid piping capacity in addition to up to 95 gallons of flexible piping capacity, allowing larger sites to achieve precision leak detection.
ELLD is a pressure-based system that uses line information to monitor changes in pressure. It determines if a line is tight or if there is a leak and will provide 3.0 gph hourly, 0.2 gph monthly, and 0.1 gph annual precision line leak detection. Here’s what you’ll need:
EVO™ 550, EVO™ 5000, EVO™ 600, and EVO™ 6000, with the TS-ELLD software option, a TS-420 input module, a TS-ACI input module, and a TS-RLY Relay module or Turbine Pump Interface (TPI).
A TS-LS500 transducer kit which plugs into the submersible. These are available in 2-, 3- or 4-line kits with cables included.
A submersible pump designed to obtain and hold a minimum static pressure of 15 psi for gross leak testing, 18 psi for precision testing, and 20 psi for learning the lines.
With AUTO-LEARN®, the TS-LS500 pressure transducer learns the characteristics of each line, eliminating possible configuration errors and ensures unparalleled leak detection accuracy.
Automatically learning the pressure characteristics eliminates the need to enter pipe lengths and diameters, removing the potential for human error.
AUTO-LEARN® makes your ELLD system tamper proof, meaning users are unable to manipulate setup parameters in order to clear alarms.
Statistical Line Leak Detection (SLLD) constantly collects hundreds of data points to ensure accurate analysis and runs in parallel with standard 3.0 gph, 0.2 gph, and 0.1 gph tests.
The SLLD feature is ideal for high throughput sites that cannot accommodate the prolonged downtime necessary for static line leak detection testing.
SLLD provides the added security of consistent precision testing and peace of mind knowing your lines are being continually tested to EPA precision levels.
* TS-RLY module is not required when utilizing turbine pump interface (TPI) communications. Franklin Electric intelligent pump controllers required.
For new installations where separate low voltage conduits can be used. Use TS-420IB Module.
Model Number | Description |
---|---|
TS-LS500/2 | 2-line transducer kit, includes installation kit |
TS-LS500/3 | 3-line transducer kit, includes installation kit |
TS-LS500/4 | 4-line transducer kit, includes installation kit |
For retrofit installations where only a high voltage conduit can be used. Use TS-420EXP Module.
Model Number | Description |
---|---|
TS-LS500E/2 | 2-line transducer kit, explosion proof, includes installation kit |
TS-LS500E/3 | 3-line transducer kit, explosion proof, includes installation kit |
TS-LS500E/4 | 4-line transducer kit, explosion proof, includes installation kit |
Model Number | Description |
---|---|
TS-AFALNIP | Leak generator needle valve kit required for E85 installations |
Title | Type | Size | |
---|---|---|---|
FFS-0263 Electronic Line Leak Detection Datasheet.pdf | 0.89 MB |
Title | Type | Size | |
---|---|---|---|
FFS-0216 (UL) FFS Product Catalog.pdf | 62.67 MB | ||
FFS-0807 (EN) Product Catalogue.pdf | 48.43 MB | ||
FFS-0367 (UL) Site Starters Ordering Guide.pdf | 52.07 MB |
Title | Type | Size | |
---|---|---|---|
10000017648 ELLD EVO_6_LLD Install_Prog Guide.pdf | 4.64 MB | ||
000-2145 LS500-EVO 550 Auto Learn Line Leak Detection Installation Guide.pdf | 2.74 MB | ||
TB0820-01 TS-LS500 Best Practices.pdf | 0.71 |